Inspection Reports - Fire Safety Format
What is the required format for fire safety system inspection reports?
Any examples are for illustrative purposes only.
The Joint Commission is not prescriptive to a specific format for fire safety system inspection records and reports. Standard EC.02.03.05/EP 28 specifies the required information that must be included on the report documenting the maintenance, testing, and inspection activities for fire alarm and fire protection systems.
The required information for each service record must include the following:
A common issue during the survey process is that the organization is not adequately familiar with the content of the report and the configuration of their fire safety systems. An effective way to accomplish this is for the testing entity to closely review the report with the organization's representative.
Additional Resources:
NFPA 25-2011: 4.3; 4.4;
NFPA 72-2010: 14.2.1; 14.2.2; 14.2.3; 14.2.4.
The Joint Commission is not prescriptive to a specific format for fire safety system inspection records and reports. Standard EC.02.03.05/EP 28 specifies the required information that must be included on the report documenting the maintenance, testing, and inspection activities for fire alarm and fire protection systems.
The required information for each service record must include the following:
- Name of the activity
- Date of the activity
- Inventory of devices, equipment, or other items
- Required frequency of the activity
- Name and contact information, including affiliation, of the person who performed the activity
- NFPA standard(s) referenced for the activity (including the edition and section)
- Results of the activity
A common issue during the survey process is that the organization is not adequately familiar with the content of the report and the configuration of their fire safety systems. An effective way to accomplish this is for the testing entity to closely review the report with the organization's representative.
Additional Resources:
NFPA 25-2011: 4.3; 4.4;
NFPA 72-2010: 14.2.1; 14.2.2; 14.2.3; 14.2.4.
Last updated on March 29, 2021
Manual:
Assisted Living Community
Chapter:
Environment of Care EC