Means of Egress - Dead-end Corridor Storage
Can dead-end corridors be used for storage or other uses?
Any examples are for illustrative purposes only.
Dead-end corridors may be used for storage only past the last door opening into the corridor so that it does not impede the means of egress. If combustible items are stored, the area used for storage is limited to a 50 square feet footprint.
Reference LS.02.01.20 EP14
Dead-end corridors may be used for storage only past the last door opening into the corridor so that it does not impede the means of egress. If combustible items are stored, the area used for storage is limited to a 50 square feet footprint.
Reference LS.02.01.20 EP14
Manual:
Office Based Surgery
Chapter:
Life Safety LS
Last reviewed by Standards Interpretation: June 28, 2023
Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016
This Standards FAQ was first published on this date.
This page was last updated on June 28, 2023
with update notes of: Review only, FAQ is current
Types of changes and an explanation of change type:
Editorial changes only: Format changes only. No changes to content. |
Review only, FAQ is current: Periodic review completed, no changes to content. |
Reflects new or updated requirements: Changes represent new or revised requirements.