Utility Systems - High Risk - Reliable Generator - Weekly Inspection

What is The Joint Commission standard for performing weekly maintenance on generators?

Any examples are for illustrative purposes only. 

NFPA 110 (2010 edition) Emergency and Standby Power Systems contains an EPSS Maintenance Schedule in Annex A that outlines the procedure and frequency for testing, inspection, and maintenance of the various components of an Emergency Power Supply System.

The requirements for the weekly emergency generator inspection required by EC.02.05.07 EP4 include an inspection of the prime mover, fuel system, lubrication system, cooling system, exhaust system, battery system, and electrical distribution system up to the automatic transfer switches. Running unloaded is not required and is discouraged because it can result in long-term problems such as wet stacking.


 
Last updated on March 19, 2021
Manual: Critical Access Hospital
Chapter: Environment of Care EC

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form
Surgeons in an operating room

Additional Resources

Train your staff with a tool to quickly and efficiently assess standards compliance with our 2021 Hospital Compliance Assessment Workbook.

A group of medical professionals have a discussion in a meeting room

Hospital Webinars

Keep learning with our Hospital Breakfast Briefings Webinar Series. Get a deep dive into our standards, chapter-by-chapter, individually or as a team.

Female doctor using digital tablet in her office.

Looking for Standards?

Get key information your hospital needs to achieve and maintain continuous standards compliance and experience operational improvement.