Emergency Power Systems - Types

What is the distinction between emergency generators, stored emergency power supply systems (SEPSS), and UPS, and when is one used versus the other?

Any examples are for illustrative purposes only.

An emergency generator can be defined as a stationary device, driven by a reciprocating internal combustion engine or turbine that serves solely as a secondary source of mechanical or electrical power whenever the primary energy supply is disrupted or discontinued. 

A stored emergency power supply system (SEPSS) is a system consisting of an uninterruptible power supply (UPS), or a motor generator, powered by a stored electrical energy source, together with a transfer switch designed to monitor preferred and alternate load power source and provide desired switching of the load, and all necessary control equipment to make the system(s) for which it is connected functional.

An uninterruptible power supply (UPS) is a device that powers equipment, nearly instantaneously allowing it to keep running for at least a short time when incoming power is interrupted. As long as utility power is flowing, it also replenishes and maintains the energy storage.

The decision to use one type over the other is usually determined by the required time for the emergency power systems to deliver electrical power. Engine driven generators can provide as long as the fuel supply is maintained.  Hospitals with heavy electrical loads for critical care patient care requiring life support equipment, lighting, HVAC and other critical systems and the need to remain functional during uncertain emergencies opt for the engine driven electrical generators. SEPSS are typically used in smaller outpatient clinics, surgical centers and ambulatory facilities due to the lower acuity of the patients and that the duration that emergency power is required to be supplied is much shorter than an in-patient facility. Emergency power is required to allow staff and patients to exit the facility, and to treatments or therapy in progress to be halted and evacuate the patients.  Runtimes for a SEPSS can be as short as a few minutes to as long as 90 minutes. Utilization of a UPS is typically to bridge the 10 second gap from power interruption to generator start time and is not to be considered a SEPSS. 
 
Additional Resources
NFPA 111 – 2010: 8.3.1; 8.3.3; 8.3.4; 8.4.1
 
Manual: Office Based Surgery
Chapter: Environment of Care EC
Last reviewed by Standards Interpretation: September 20, 2024 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on September 20, 2024 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.