ILSM - Policy Scope
What must an Interim Life Safety Measure policy contain?
Any examples are for illustrative purposes only.
In order to evaluate and implement an effective plan for Life Safety code deficiency mitigation, an Interim Life Safety Measure
(ILSM) policy must consist of the following:
In order to evaluate and implement an effective plan for Life Safety code deficiency mitigation, an Interim Life Safety Measure
(ILSM) policy must consist of the following:
- State that the process is applicable to construction related situations and situations of non-compliance with the Life Safety Code.
- State circumstances that would require ILSM assessment, to include a statement that at all Statement of Condition, Plans for Improvement (PFIs) are to be assessed for ILSM.
- Describe how the organization will respond to situations described in LS.01.02.01.
- Describe how occupants are to be protected by using the available menu of interim life safety measures described in LS.01.02.01, as applicable to the situation.
- Describe the ILSM assessment process, to include an assessment tool to document which measure(s) will be implemented.
- Describe the ILSM implementation process, to be effective throughout the duration of the deficiency(s), and to include an implementation tool to document each implemented ILSM for the duration of its application.
Manual:
Nursing Care Center
Chapter:
Life Safety LS
New or updated requirements last added: November 13, 2023.
New or updated requirements may be based on revisions to current accreditation requirements, regulatory changes, and/or an updated interpretation in response to industry changes. Substantive changes to accreditation requirements are also published in the Perspective Newsletter that is available to all Joint Commission accredited organizations.
Last reviewed by Standards Interpretation: November 13, 2023
Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016
This Standards FAQ was first published on this date.
This page was last updated on November 13, 2023
with update notes of: Reflects new or updated requirements
Types of changes and an explanation of change type:
Editorial changes only: Format changes only. No changes to content. |
Review only, FAQ is current: Periodic review completed, no changes to content. |
Reflects new or updated requirements: Changes represent new or revised requirements.