Life Safety Code Floor Plans - Business Occupancies
Are Life Safety Code floor plans required for business occupancies?
Any examples are for illustrative purposes only.
LS.01.01.01 EP3 requires a hospital/organization to maintain "current and accurate drawings denoting features of fire safety and related square footage."
Where the entire building is considered business occupancy by the definition of NFPA 101 (2012 edition) Life Safety Code, life safety drawings are not required . For mixed occupancy buildings where portions of the building are business occupancy, and other portions are either health care occupancy or ambulatory health care occupancy, life safety drawings are required for the whole building, including the sections that are business occupancy.
For hospitals and ambulatory health care facilities, LS.01.01.01 EP 7 requires that "the hospital/organization maintains current Basic Building Information (BBI) within the Statement of Conditions (SOC)." Organizations that have free-standing business occupancy buildings shall list them in the SOC under "Sites and Buildings."
Reference LS.01.01.01 EP3, EP7
LS.01.01.01 EP3 requires a hospital/organization to maintain "current and accurate drawings denoting features of fire safety and related square footage."
Where the entire building is considered business occupancy by the definition of NFPA 101 (2012 edition) Life Safety Code, life safety drawings are not required . For mixed occupancy buildings where portions of the building are business occupancy, and other portions are either health care occupancy or ambulatory health care occupancy, life safety drawings are required for the whole building, including the sections that are business occupancy.
For hospitals and ambulatory health care facilities, LS.01.01.01 EP 7 requires that "the hospital/organization maintains current Basic Building Information (BBI) within the Statement of Conditions (SOC)." Organizations that have free-standing business occupancy buildings shall list them in the SOC under "Sites and Buildings."
Reference LS.01.01.01 EP3, EP7
Manual:
Nursing Care Center
Chapter:
Life Safety LS
Last reviewed by Standards Interpretation: July 12, 2023
Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016
This Standards FAQ was first published on this date.
This page was last updated on July 12, 2023
with update notes of: Review only, FAQ is current