Medication - Sterile Compounding - Secondary Engineering Control (SEC) Testing/Certification Requirements

What testing is required for our Secondary Engineering Controls ?

Any examples are for illustrative purposes only.

The following items are expected to be tested at a minimum with a frequency not to exceed 6 month intervals.  Lack of testing of these items will result in non-compliance with Joint Commission standards.
• Air exchanges per hour of the buffer area
• Pressure differential (between buffer area/ante area; ante area/non-classified area)
• ISO level of the buffer area and ante area
• Viable particle testing surface of the buffer area and ante area
• Viable particle testing air—HEPA filter leak test of HVAC HEPA filter system
• Evidence of remediation/retesting if assessed levels were not in compliance with those listed in USP 797
Last updated on May 11, 2020
Manual: Critical Access Hospital
Chapter: Medication Management MM

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form
Surgeons in an operating room

Additional Resources

Train your staff with a tool to quickly and efficiently assess standards compliance with our 2021 Hospital Compliance Assessment Workbook.

A group of medical professionals have a discussion in a meeting room

Hospital Webinars

Keep learning with our Hospital Breakfast Briefings Webinar Series. Get a deep dive into our standards, chapter-by-chapter, individually or as a team.

Female doctor using digital tablet in her office.

Looking for Standards?

Get key information your hospital needs to achieve and maintain continuous standards compliance and experience operational improvement.