Utility Systems - High Risk - Reliable Generator - Weekly Inspection
What is The Joint Commission standard for performing weekly maintenance on generators?
Any examples are for illustrative purposes only.
NFPA 110 (2010 edition) Emergency and Standby Power Systems (EPSS) contains a Maintenance Schedule in Annex A that outlines the procedure and frequency for testing, inspection, and maintenance of the various components of an Emergency Power Supply System.
The requirements for the weekly emergency generator inspection required by EC.02.05.07 EP4 include an inspection of the prime mover, fuel system, lubrication system, cooling system, exhaust system, battery system, and electrical distribution system up to the automatic transfer switches. Running unloaded is not required and is discouraged because it can result in long-term problems such as wet stacking.
NFPA 110 (2010 edition) Emergency and Standby Power Systems (EPSS) contains a Maintenance Schedule in Annex A that outlines the procedure and frequency for testing, inspection, and maintenance of the various components of an Emergency Power Supply System.
The requirements for the weekly emergency generator inspection required by EC.02.05.07 EP4 include an inspection of the prime mover, fuel system, lubrication system, cooling system, exhaust system, battery system, and electrical distribution system up to the automatic transfer switches. Running unloaded is not required and is discouraged because it can result in long-term problems such as wet stacking.
Manual:
Ambulatory
Chapter:
Environment of Care EC
First published date: April 11, 2016
This Standards FAQ was first published on this date.
This page was last updated on June 08, 2023
with update notes of: Editorial changes only
Types of changes and an explanation of change type:
Editorial changes only: Format changes only. No changes to content. |
Review only, FAQ is current: Periodic review completed, no changes to content. |
Reflects new or updated requirements: Changes represent new or revised requirements.